12 April 2004 Experimental study of radiant-heat blocking function of fine water mist suppressing small-scale pool fire
Author Affiliations +
Abstract
Fine water mist with droplet diameter less than 20 microns is less studied in water mist family used as firefighting agent. Experiments were conducted to study the radiant heat blocking function of fine water mist in suppressing pool fire. The fine water mist was generated by a jet atomizer. The jet flow of mist was with low momentum when it exerted on the pool fire. The interaction of this kind of fine water mist with pool fire is quite different from those mists with large droplet size and momentum. A group of ethyl-alcohol and gasoline pool fires with different power is used in the research. Fine water mist was exerted on the pool fire from different distances. Radiant heat flux was measured before and after the mist application. The experiment results show that because of its small droplet size and low momentum, the fine water mist could not even penetrate the buoyant plum zone of relatively larger scale pool fire. No water mist could reach the surface of the flame and result in no radiant heat blocking function would realize in the flame zone. This function is valid in low power pool fire and this limitation is obtained from the research for the studied pool fire.
© (2004) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Qiang Xu "Experimental study of radiant-heat blocking function of fine water mist suppressing small-scale pool fire", Proc. SPIE 5405, Thermosense XXVI, (12 April 2004); https://doi.org/10.1117/12.538236
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Heat flux

Signal attenuation

Time-frequency analysis

Combustion

Distance measurement

Glasses

Liquids

Back to Top